| Technical
Notes 3 - Overview of Building Code Requirements for Masonry
Structures (ACI 530-02/ASCE 5-02/TMS 402-02) and Specification for
Masonry Structures (ACI 530.1-02/ASCE 6-02/TMS 602-02) July 2002 Key Words: adhered veneer,
allowable stress design, anchored veneer, building code, design
standard, empirical design, inspection, prestressed masonry,
specification, strength design. INTRODUCTION The American Concrete Institute (ACI),
American Society of Civil Engineers (ASCE), and The Masonry
Society (TMS) promulgate a national consensus standard for the
structural design of masonry elements and a standard specification
for masonry construction. These standards are titled the Building
Code Requirements for Masonry Structures (ACI 530/ASCE 5/TMS
402) and the Specification for Masonry Structures (ACI
530.1/ASCE 6/TMS 602). They were developed to consolidate
and advance existing standards for the design and construction of
masonry. This Technical Notes, the first
in a series, discusses various sections of the Building Code
Requirements for Masonry Structures and the Specification
for Masonry Structures in brief detail. Emphasis
is placed on the new requirements in the 2002 edition of the
standards. Changes from prior masonry standards dealing with
the design of brick masonry structures are also presented.
Other Technical Notes in this series provide material and
section properties of brick masonry members and more extensive
discussion of the requirements of these standards. For more
information about the requirements of these standards and examples
of their application, the reader is referred to the Masonry
Designer's Guide (MDG). The MDG is published by The
Masonry Society and contains an extensive number of design
examples that illustrate the proper application of the MSJC Code
and Specification requirements. In this Technical Notes, the Building
Code Requirements for Masonry Structures and the Specification
for Masonry Structures are referred to as the Masonry
Standards Joint Committee (MSJC) Code and Specification,
respectively. The pertinent section and article numbers from
the MSJC Code and Specification, are stated in parentheses
following the discussion of particular topics for quick reference. HISTORY AND DEVELOPMENT The development of this single masonry
standard for the design and construction industry began in 1977.
At that time, there were several design standards for masonry.
These standards did not have consistent requirements. It was
difficult for engineers and architects to select the appropriate
design criteria for masonry elements. Concerned individuals
representing masonry materials and the design profession saw the
need for a single, national consensus standard for the design and
construction of all types of masonry. In 1977, ACI and ASCE agreed to jointly develop a consensus
standard for masonry design with the support of the masonry
industry. The MSJC was formed with a balanced membership of
building officials, contractors, university professors,
consultants, material producers and designers who are members of
ACI or ASCE. The Masonry Society joined as a sponsoring
organization in 1991. Currently, the MSJC is comprised of
over eighty regular (voting) and forty associate members.
The MSJC Code and Specification are available from each of the
sponsoring organizations or from the Brick Industry Association. Changes to the MSJC Code and
Specification are written, balloted and approved within the MSJC.
A review by the sponsoring organizations' technical activity
committees follows. In order to obtain a national consensus,
the approved draft undergoes a public review. Approval by
the MSJC of the first edition of the MSJC Code and Specification
occurred in June 1986. Public review began in 1988 with the
final approval of the 1988 MSJC Code and Specification in August
1989. Commentaries for the MSJC Code and
Specification were also developed. These documents provide
background information on the design and specification provisions.
Considerations of the MSJC members in determining requirements and
references to research papers and articles are included in the
commentaries for further information. The MSJC Code, Specification and
Commentaries are revised on a three- or four-year cycle. The
first revision was issued in 1992. Most of the changes were
editorial in nature or clarified intent or omissions. In
1995 new chapters on glass unit masonry and anchored masonry
veneers were added, and the MSJC Specification was reformatted.
Metric conversions were added throughout the standards in
accordance with the metrication policy of ASCE in addition to an
index of key words. The 1999 edition includes a number of
significant changes. The MSJC Code and its Commentary were
reformatted. A chapter on prestressed masonry, a section on
adhered veneer and a quality assurance program were added.
Other changes in the MSJC Code and Specification include new
design values for elastic moduli and masonry compressive strength
and the inclusion of mortar cement. In the 2002 edition
there were significant changes to the seismic design provisions,
with prescriptive requirements for specific shear wall types.
A chapter on strength design was added. Other minor changes
are documented in this Technical Notes. Building Code Acceptance The MSJC Code is to be adopted by a
model building code and, subsequently, by a local jurisdiction.
State and local building code committees are encouraged to adopt
the model building codes which include the MSJC Code for the
design of masonry. With adoption of the MSJC Code, the
Specification is automatically adopted because the MSJC Code
requires that materials and construction comply with the MSJC
Specification. The local jurisdiction has the responsibility
for enforcement and compliance of masonry construction to the MSJC
Specification once it is adopted. Two of the previous model building code
organizations, the Standard Building Code Congress International (SBCCI)
and the Building Officials and Code Administrators (BOCA), chose
to include the MSJC Code in their documents. This adoption by
reference began in 1988 and1989, respectively. The International
Council of Building Officials (ICBO) chose to maintain masonry
design criteria within the Uniform Building Code itself,
rather than adopting the MSJC standards by reference.
However, many of the masonry design and construction requirements
of the Uniform Building Code have been changed over the
last several years to be consistent with the requirements of the
MSJC Code and Specification. The International Code Council (ICC)
was formed by the three existing code organizations (SBCCI),
(BOCA) and (ICBO) with the charge to produce a single set of
codes, referred to as the I-codes. Two I-codes that are
important to the brick industry are the International Building
Code (IBC) and International Residential Code (IRC). The
National Fire Protection Association (NFPA) is also developing
another building code called NFPA 5000. The I-codes and NFPA
5000 reference the 2002 MSJC Code. Benefits The MSJC Code and Specification have
had positive results; the design and construction community has
become more confident with their use. Designers have one
national standard that covers nearly all types of masonry
construction. Architects are able to prepare and submit
complete, concise specifications more easily. Contractors
have more consistent and better quality specifications for
projects. Owners obtain more uniform quality of masonry.
Other benefits presented by the MSJC Code and Specification are:
Since the introduction of the MSJC
standards in 1988, there has been a shift in the masonry design
and construction communities. Designers and contractors use
the MSJC Code and Specification with more frequency.
Indicative of this growth, the MSJC Code is now a required
reference for the Professional Engineer's Principles and
Practice examination. The MSJC Specification has placed
greater demands on the masonry contractor with the use of masonry
as a structural material. Many requirements are performance
related, which may require more site inspection for verification
of compliance. These demands are advantageous and vital to
the development of confidence that the masonry strengths assumed
by the designer are met by the constructed masonry. THE MSJC CODE (ACI 530/ASCE 5/TMS
402) The MSJC Code is the basis for masonry
design by the architect or engineer. The provisions of the
MSJC Code will dictate the size and shape of masonry walls, beams,
pilasters and columns. Further, it influences the masonry
materials the designer will require in the project specification.
It consists of seven chapters, which are listed below. Chapter 1 - General Design Requirements
for Masonry Chapter 2 - Allowable Stress Design Chapter 3 - Strength Design of Masonry
(New Chapter) Chapter 4 - Prestressed Masonry Chapter 5 - Empirical Design of Masonry Chapter 6 - Veneer Chapter 7 - Glass Unit Masonry Some relevant sections of the codes are
discussed in this Technical Notes and are indicated in
parentheses for each of the chapters. Chapter 1 - General Design
Requirements for Masonry Chapter 1 contains the scope of the
minimum requirements for the design of any masonry element.
In this chapter, it states that the MSJC Code supplements the
model building code enforced in a jurisdiction. When the
MSJC Code conflicts with the local building code, the local
building code governs. (1.1) Project drawings and specifications
must identify the individual responsible for their preparation.
Items required by the MSJC Code must be clearly marked such as:
loads used in design, specified compressive strength of masonry,
reinforcement, anchors and ties with size and spacing, size and
location of all structural elements, provisions for differential
movement, and size and location of conduit, pipes and sleeves.
Contract documents must include a quality assurance program. (1.2) The MSJC Code permits alternative
design methods from those stated in the MSJC Code. This is
to recognize new applications of masonry and different structural
analysis techniques. (1.3) Chapter 1 also includes the notation
and definitions contained within the MSJC Code. Capital
letters are used for permitted stresses and lower case letters are
used for calculated or applied stresses. (1.5) For example, Fa is
the notation for the allowable compressive stress due to axial
load, while fa denotes the calculated compressive
stress due to axial load. The definitions are specifically
related to their meaning as used in the MSJC Code.
Definitions in the MSJC Code are coordinated with those in the
MSJC Specification. Definitions of terms relating to
strength design of masonry and for prestressed masonry have been
added. (1.6) The following are brief summaries,
highlights, of several sections within Chapter 1. Section 1.7 - Loading.
Service loads are used as the basis of design and are governed by
the building code that adopts the MSJC Code. If a building
code is not enforced in the area under consideration, then the
MSJC Code requires that the load provisions of the 1993 edition of
ASCE 7 Design Loads for Buildings and Other Structures
apply to masonry structures. Allowable stresses given in the
MSJC Code are based on failure stresses with a factor of safety in
the range of 2 to 5. The structural system must resist wind
and earthquake loads and accommodate the resulting deformations.
(1.7.3) The effects of restraint of movement due to prestressing,
vibrations, impact, shrinkage, expansion, temperature changes,
creep, unequal settlement of supports and differential movement
must also be considered in design. (1.7.4) Section 1.8 - Material
Properties. Material properties are included for both clay
and concrete masonry. The MSJC Code and Specification was
the first national masonry standard to state design coefficients
for thermal expansion, moisture expansion, shrinkage and creep.
For design computations, the amount of shrinkage of brick masonry
is taken as zero. The moduli of elasticity, Em, of
clay and concrete masonry is no longer based on the net area
compressive strength of the brick and the type of mortar used in
construction. Em is now directly related to the
specified compressive strength of masonry, f'm.
For clay masonry, Em is equal to 700 times f'm.
Alternately, Em may be determined by the chord modulus
of elasticity taken between 0.05 and 0.33 of the maximum
compressive strength of each prism determined by test in
accordance with Article 1.4 B.3 of the MSJC Specification.
Refer to Technical Notes 18 Series for an extensive
discussion of differential movement of brick masonry elements.
(1.8.2.2) Section 1.9 - Section
Properties. Section properties are used to determine stress
computations. Computations for stiffness, radius of gyration
and flange design for intersecting walls are based on the minimum
net area of the section. This is normally the mortar-bedded
area. When different materials are combined in a single
element, the transformed area must be used to account for
differences in elastic moduli of the dissimilar materials.
Radius of gyration of the section, rather than the minimum
thickness, is used to determine the slenderness reduction for
members in compression. (1.9) Section 1.10 - Deflection. Deflection
limits are imposed for beams and lintels that support unreinforced
masonry. The deflection should not exceed the span length
divided by 600 or 0.3 in. (7.6 mm). Deflection of the
masonry member should be calculated based upon uncracked section
properties. (1.10, 1.9.2) Section 1.11 - Stack Bond
Masonry. The MSJC Code requires that stack bond masonry be
reinforced with a prescriptive amount of horizontal reinforcement.
This may be placed as joint reinforcement or in bond beams spaced
not more than 48 in. (1.2 m) on center vertically. (1.11) Section 1.12 - Details of
Reinforcement. The reinforcement detailing requirements
given in this chapter are similar to those for reinforced concrete
under ACI 318, Building Code Requirements for Reinforced Concrete.
The maximum size of reinforcing bar permitted in masonry members,
designed by the allowable stress or empirical design methods, is a
No. 11 (M #36) bar. Horizontal joint reinforcement is
permitted as structural reinforcement for the same design methods.
Placement limits for reinforcement include minimum grout spaces
between the bars and masonry units of 1/4 in. (6.4 mm) and 1/2 in.
(12.7 mm) for fine and coarse grout, respectively. (1.12.2 -
1.12.3) This section contains protection
requirements for reinforcing steel. A minimum amount of
masonry cover is required, depending upon the exposure conditions.
Corrosion protection is required for joint reinforcement, wall
ties, anchors and inserts in exterior walls. (1.12.4) Minimum development lengths are stated
for reinforcement. A 50 percent increase is recommended for
epoxy coated bars. (2.1.10.2) Standard hooks, minimum bend
diameters, and splice requirements are consistent with those for
reinforced concrete members. (1.12.5, 1.12.6) Chapter 3
contains variations in some of these requirements when strength
design is used. Section 1.13 - Seismic Design
Requirements. These requirements apply to the design and
construction of all masonry, except glass unit masonry and masonry
veneers, for all Seismic Design Categories (SDC) as defined in
ASCE 7-98. Early editions of the MSJC included seismic
design information as optional information in the Appendix and
based the requirements on Seismic Zones. Since 1995, the
seismic requirements are mandatory parts of the Code.
Seismic provisions for masonry veneers are found in Chapter 6,
Veneers. Special seismic requirements in Section 1.13 are invoked by
SDC. The requirements are additive for each higher SDC.
For example, buildings in category D must meet all the
requirements for buildings in categories A, B and C, plus the
additional requirements stated in Section 1.13 for buildings in
category D. Five types of shear walls that serve as the lateral
force-resisting system are described. Each has a required
design method and prescriptive reinforcement requirements, see
Table 1. Their use is permitted by the seismic design
category applicable to the structure under design. TABLE 1 Requirement for Masonry Shear Walls Based on Shear Wall
Designation
In category A, the
provisions of Chapters 2, 3, 4, or 5 of the MSJC Code apply.
There is a calculated story drift limit of 0.007 times the story
height. Anchorage of masonry walls must meet a minimum
design force of 1000 times the effective peak velocity-related
acceleration. (1.13.3) For buildings in category B, the
lateral force-resisting system must comply with the requirements
of Chapter 2, 3, or 4 of the MSJC Code. It cannot be
designed in accordance with the empirical requirements of Chapter
5. The lateral force-resisting system includes structural
masonry members such as columns, beams and shear walls. It
does not include non-loadbearing elements, such as partition
walls. (1.13.4) Masonry buildings in category C must
meet more stringent requirements. Members that are not part
of the main lateral force-resisting system must be isolated so
that they do not adversely affect the response of the lateral
force-resisting system. Connections are strengthened and
minimum amounts of reinforcement are required for shear walls and
non-loadbearing masonry members in order to provide more ductility
to the structure. (1.13.5) Partition walls, screen walls and
other elements that are not designed to resist vertical or lateral
loads other than their own weight must be isolated from receiving
these loads and designed to accommodate drift. The special seismic provisions for
categories D and E are still more restrictive. Minimum
reinforcement requirements are increased for all members.
Type N mortar and masonry cement mortars are not permitted for the
lateral force-resisting system. (1.13.6, 1.13.7) Section 1.14 - Quality Assurance. This
section defines a quality assurance program with different
requirements based on the type of facility and method of design.
Minimum tests, submittals and inspection requirements are defined
for three levels of quality assurance. (1.14.1) The quality assurance program must include procedures for
reporting, review and resolution of noncompliances. (1.14.5)
Qualifications for testing laboratories and for inspection
agencies must also be defined. (1.14.6) The quality assurance program requires
that each wythe of masonry and the grout, if present, must meet or
exceed the specified compressive strength of masonry, f'm.
Compressive strength of masonry must be verified in accordance
with the provisions of the MSJC Specification. (1.14.2) Section 1.15 - Construction. Construction of masonry
must comply with the MSJC Specification. Requirements for
grouting are introduced in Section 1.15. The type of grout,
either fine or coarse, determines the minimum grout space
dimensions and maximum grout pour height permitted. New in
the 2002 edition is the inclusion of a grout demonstration panel.
The limits can be exceeded if the panel indicates that the spaces
are filled and adequately consolidated. Grout must attain a
minimum compressive strength of 2000 psi (13.8 MPa) at 28 days.
(Table 1.15.1) In addition, Section 1.15 contains
provisions for pipes and conduits embedded in masonry elements.
The effect on structural performance of the opening caused by the
embedded item must be considered. Limitations on location,
size, relative area and materials contained within pipes and
conduit are included. (1.15.2) Chapter 2 - Allowable Stress
Design Allowable stress design (ASD)
methodology has been used in masonry design for many years.
The ASD provisions of the MSJC Code are the most advanced to date
for masonry members and are reflective of the extensive amount of
research and experience gained over the last century. Chapter 2 of the MSJC Code states
general provisions and establishes the scope of the rational
design requirements. The rational design provisions are
based upon a few assumptions inherent in the ASD approach, which
are as follows:
Service loads are used as the basis of
allowable stress design. Allowable stresses given in the
MSJC Code are based on failure stresses with a factor of safety in
the range of 2 to 5. Section 2.1.2 contains the loading
combinations to be used for allowable stress design. For
moment strength design under Section 4.5.3.3.2, factored loads
shall be combined as required by the general building code.
When the general building code does not provide load combinations,
structures or members shall use the most restrictive combinations
of loads. (2.1.2) The specified compressive strength of
masonry, f'm, must be determined by the designer and
clearly stated in the contract documents. The specified
compressive strength must be verified by the contractor as
required by the methods stipulated in the MSJC Specification.
(2.1.3) Anchor bolts consist of plate, headed
and bent bar assemblies. Allowable loads for tension, shear
and combined tension and shear are given. Provisions for
minimum embedment length are provided to ensure proper transfer of
load between the masonry and the anchor bolt. (2.1.4) Refer
to Technical Notes 44 for further discussion of the design
of anchor bolts. The MSJC Code requirements
differentiate between multiwythe walls with respect to composite
or non-composite action. Composite action requires a rigid
transfer of stress between wythes so that the wythes act as a
single element in resisting loads. The wythes must be bonded
with a filled collar joint and metal ties or with masonry headers.
Prescriptive size and spacing limitations for metal wall ties are
taken from previous masonry standards. For multiwythe,
composite walls, criteria for allowable shear stresses at the
interface between a wythe and a collar joint have been introduced
that were not included in previous masonry standards. These
allowable shear stresses are: a) 5 psi (34.5 kPa) for mortared
collar joints, b) 10 psi (69.0 kPa) for grouted collar joints, and
c) the square root of the unit compressive strength of the header.
(2.1.5.2.2) When non-composite action occurs, each
wythe is designed to individually resist the effects of imposed
loads. Loads are apportioned to wythes based upon their
relative stiffnesses. As with composite walls, prescriptive
requirements for metal wall ties are based on past experience.
(2.1.5.3 ) Wall ties with drips are now prohibited. Columns are isolated vertical members
whose horizontal dimension at right angles to the thickness does
not exceed 3 times its thickness. Also, the member's
height must be at least 3 times its thickness. The minimum
dimension of a column is 8 in. (203 mm) and the maximum ratio of
effective height to least nominal dimension (slenderness ratio) of
a column is 25. Columns must contain a minimum of four
vertical reinforcing bars and a minimum amount of lateral ties.
(2.1.6) Pilasters are thickened elements of a wall which provide resistance to lateral loads or a combination of axial and lateral loads. Design procedures consider the pilaster and wall to act integrally, provided the two are properly bonded. Vertical reinforcement that is intended to resist axial loads must be laterally tied in the same manner that is required for columns. (2.1.7) Concentrated loads must be distributed over a prescribed length of wall. Requirements depend on bond pattern, presence of bond beams and the width of the wall. The allowable bearing stress is one-fourth of the specified compressive strength of masonry, but may be increased for smaller bearing areas. (2.1.9)Provisions for development of
reinforcement are included. (2.1.10) Bars, hooks,
welded wire fabric, and splices are covered. Section 2.2 - Unreinforced
Masonry. Section 2.2 covers requirements for the design of
masonry structures in which tensile stresses in masonry are taken
into consideration. This is known as unreinforced (plain)
masonry. Such members may, in fact, contain reinforcement
for shrinkage or other reasons, but this reinforcement is
neglected in the structural design process. The allowable axial compressive stress
equation uses a different slenderness reduction factor from that
used in earlier masonry standards. The factor is a function
of the radius of gyration of the member's cross section, rather
than its thickness. Additionally, the factor of safety
changed from 5 in previous masonry standards to 4 in the MSJC
Code. Unlike previous masonry design standards, the MSJC
Code does not place an arbitrary limit on the slenderness ratio of
walls. Rather, the slenderness reduction factor becomes very
small for more slender walls. An equation limiting the
applied axial load to one-quarter of a modified Euler buckling
load is included. The classic Euler buckling load has been
modified to reflect a member with negligible tensile strength.
The unity equation has been used to limit the combination of
bending and axial load in masonry design for many years. (2.2.3,
2.3.3) Variables affecting flexural tension of
masonry include the plane on which the stress acts, mortar
materials, unit cross-section, and presence of grout. The
allowable flexural tension stresses for grouted masonry normal to
bed joints were modified in the 2002 edition. (2.2.3.2) Allowable shear stresses are based upon
a parabolic shear stress distribution rather than an average shear
stress distribution, as used in previous masonry standards.
Consequently, allowable shear stresses are approximately 1.5 times
those in previous masonry standards. Four allowable shear
stresses for in-plane shear must be evaluated. No allowable
shear stress values are given for out-of-plane shear, but
typically these same values for in-place shear are applied.
(2.2.5) Section 2.3 - Reinforced Masonry.
Section 2.3 contains requirements for the allowable stress design
of masonry elements neglecting the tensile strength of masonry.
This is commonly termed reinforced masonry. In this
procedure, steel reinforcement is used to resist all tensile
forces. Reinforcement may also be required to resist shear
forces. The MSJC Code does not prescribe a minimum amount of
reinforcement, except for masonry columns and for buildings in
Seismic Design Categories as given in Chapter 1. The size
and placement of compressive, flexural and shear reinforcement is
determined by design requirements. (2.3.1) Allowable steel
stresses are taken from previous masonry standards.
Reinforcement used to resist compressive stresses must be
laterally tied. (2.3.2.2) When the applied shear stress exceeds
the given allowable shear stress for reinforced masonry without
shear reinforcement, shear reinforcement is required. For
reinforced masonry containing shear reinforcement, allowable shear
stresses are increased by a factor of 3.0 for flexural members and
1.5 for shear walls. To use the increased allowable shear
stresses, shear reinforcement must be provided to resist 100
percent of the shear force. (2.3.5) Chapter 3 - Strength Design of Masonry This chapter is new in the 2002 edition
of the MSJC Code. This chapter was developed from research
funded by the National Science Foundation and the masonry
industry. Strength design identifies the possible
failure modes that the masonry element can exhibit. By
performing this type of analysis the engineer can preclude an
undesirable failure. Strength design provides for design of
inelastic performance of masonry. The loads and stresses
considered are similar to those used in allowable stress design,
but service level loads are replaced with strength design loads
and allowable stresses are replaced with nominal values based on
research. The required strength of the masonry must be
greater than its nominal strength multiplied by a strength
reduction factor, Ø. The strength reduction factors
selected are similar to those used in concrete. Strength design of masonry shall comply
with the minimum requirements of this chapter. In addition,
the requirements of Chapter 1, Section 3.1, and either Section 3.2
or 3.3 also apply. (3.1.1) The strength requirements are in
accordance with the legally adopted building code. When this
information is not defined in the building code then the
requirements of ASCE 7-98 govern. (3.1.2) Notations and
definitions used in strength design are found in Sections 1.5 and
1.6, respectively. The remainder of Chapter 3 covers
design strength (3.1.3), strength reduction factors (3.1.4),
deformation requirements (3.1.5), headed and bent-bar anchor bolts
(3.1.6), material properties (3.1.7), reinforced masonry (3.2),
and unreinforced (plain) masonry (3.3). Design equations are
similar to those for allowable stress design when possible.
Perhaps the most significant difference is in the development
length. The strength design formula includes cover, bar
size, and masonry specified compressive strength as variables.
This formula also applies to splices. This chapter includes maximum
reinforcement ratios chosen to prevent brittle failure of shear
walls. These are applied with specific limits on strain in
the masonry and steel. There are also dimensional limits for
beams, piers, and columns. It must be pointed out that Strength
Design of Masonry may not be practical in many situations and may
in fact not provide the results a designer may seek. Chapter 4 - Prestressed Masonry Prestressed masonry is used to eliminate tensile stresses in
masonry due to externally applied loads. A controlled amount
of precompression is applied to the masonry to offset the tensile
forces created under service loads. The use of prestressing
is well documented in concrete design and construction; however
its use in masonry construction in the United States is limited.
The United Kingdom has a history of successful prestressed masonry
construction for over two decades. The equipment for prestressed masonry is similar to that used
in concrete construction. Some proprietary systems have been
developed specifically for use in prestressed masonry. Types
of structures that have utilized prestressed masonry in the United
States include freestanding walls, such as fences, bearing walls
and masonry veneers designed to span between columns, rather than
span floor-to-floor. Prestressing tendons placed in openings in the masonry may be
grouted or ungrouted. The tendons may be pre-tensioned or
post-tensioned. Pre-tensioned tendons are stressed against
external abutments prior to placing the masonry.
Post-tensioned tendons are stressed against the masonry after it
has been placed. Most construction applications to date have
been post-tensioned, ungrouted masonry because of the ease of
construction and overall economy. As a result, the MSJC Code
focuses primarily on post-tensioned masonry. Chapter 4 provides minimum requirements for the design of
structures that are prestressed with bonded or unbonded
prestressing tendons. The general design requirements found in
Chapter 1, including seismic provisions, apply to prestressed
masonry with a few modifications. (4.1) Prestressed members
are designed using elastic analysis and allowable stress design.
A new term, f'mi, is defined as the specified
compressive strength of masonry at the time of transfer of the
prestress force. (4.2) The remainder of Chapter 4 covers permissible stresses in the
prestressing tendons, effective prestress, axial compression and
flexure, axial tension, shear, deflection, prestressing tendon
anchorages, couplers, end blocks, protection of prestressing
tendons and accessories, and development of bonded tendons. Chapter 5 - Empirical Design of
Masonry Chapter 5 presents empirical
requirements for masonry structures. These requirements are
based on past proven performance. Configuration of masonry
structures for compliance with empirical limits is a technique
that predates rational design methods. The empirical
provisions of previous masonry standards have been modified and
advanced in Chapter 5 to reflect contemporary construction
materials and methods. The requirements are essentially
unchanged from the 1999 edition. The empirical requirements in Chapter 5
may be applied to the following masonry elements:
The empirical requirements may not be
applied to structures resisting horizontal loads other than those
due to wind or seismic events, except that foundation walls may be
as permitted in Section 5.6.3. The empirical requirements
for foundation walls include limits on the height of backfill.
There are a number of restrictions on the backfill soil and the
configuration of cross walls. (5.6.3.1) The 2002 Code also
requires foundation piers to be a minimum of 8 in. (203 mm) in
thickness. (5.6.4) The empirical requirements of the MSJC
Code are discussed in Technical Notes 42 Revised. Chapter 6 - Veneers. The requirements of Chapter 6 apply to
masonry veneers. In the 2002 MSJC Code, provisions address
anchored masonry veneer and adhered masonry veneer. The
requirements of this chapter are especially important to the brick
industry as the majority of brick produced in the United States is
used as veneer. Section 6.2 - Anchored veneer.
The majority of this chapter contains prescriptive requirements
for masonry veneer, but alternative design methods are permitted.
(6.2.1) The prescriptive requirements cannot be used in
areas where the wind speed exceeds 110 mph (145 km/hr) as given in
ASCE 7-98. (6.2.2.1) Many of the requirements are based upon
those found in Technical Notes 28 Series on brick veneer
walls and Technical Notes 44B on wall ties.
(6.2.2.3-6.2.2.9) Seismic requirements are included for
buildings in SDC C, D, and E. (6.2.2.10) Section 6.3 - Adhered veneer.
Adhered veneer can be designed by the prescriptive requirements
contained in this section or by alternative design methods.
(6.3.1) Prescriptive requirements found in the 2002 MSJC
Code are based on similar requirements that have been used in the
Uniform Building Code for over 30 years. These requirements
limit unit size to no more than 2 5/8 in. (66.7 mm) in specified
thickness, 36 in. (914 mm) in any face dimension and 5 ft2
(0.46 m2) in total face area. The weight of
adhered veneer units is limited to15 lbs/ft2 (718 Pa).
(6.3.2) Adhesion between the veneer units and
the backing must have a shear strength of 50 psi (345 kPa) or
greater based on gross unit surface area when tested in accordance
with ASTM C 482. Alternatively, adhered units may be applied
using the procedure found in MSJC Specification Article 3.3C.
(6.3.2.4) Chapter 7 - Glass Unit Masonry
Chapter 7 applies to glass unit
masonry. The 2002 edition contains few changes from the 1999
version. The provisions are largely based upon those in the
three previous model building codes. Requirements are
primarily prescriptive and empirical. Maximum wall areas are imposed by a
design wind pressure graph for standard units, 3 7/8
in. (98.4 mm) thick. When 3 in. (76.2 mm) thick units are
used, a maximum wind pressure of 20 psf (958 Pa) is imposed and
the maximum wall area is reduced. The size of interior wall
panels is limited to 250 ft2 (23.22 m2) and 150 ft2 (13.94
m2) for standard and thin units, respectively. (7.1, 7.2)
Provisions regarding lateral support for panels limited to one
unit wide or one unit high are included. (7.3) The MSJC Code also imposes requirements
for expansion joints. (7.4) Base surface treatment requires the
surface on which glass unit masonry panels are placed to be coated
with an elastic waterproofing material. (7.5) Glass unit masonry shall be built with
Type S or N mortar. (7.6) Glass unit masonry panels must contain
a minimum amount of horizontal joint reinforcement. The MSJC
Code requires a minimum of two parallel W1.7 (MW11) wires spaced
at 16 in. (406 mm) o.c. vertically. Joint reinforcement is
very important because the limitations on wall panel size are
based upon the failure of the reinforced section, rather than the
first cracking strength of panels. (7.7) THE MSJC SPECIFICATION (ACI 530.1/ASCE
6/TMS 602) The MSJC Specification is a reference
standard that an architect or engineer may cite in the contract
documents for any project. The MSJC Specification contains
requirements for the contractor regarding materials, construction
and quality assurance. The MSJC Code requires compliance of
construction of the masonry with the MSJC Specification, so it is
an integral part of the MSJC Code. The language is in
imperative voice for ease of interpretation and enforcement.
The MSJC Specification should be referenced in the contract
documents and may be modified as required for the particular
project. The 2002 edition of the MSJC
Specification consists of three components: a) Part 1 - General,
b) Part 2 - Products and c) Part 3 - Execution. The format
was changed to the present one in 1995 to be more consistent with
the Construction Specifications Institute's MASTERFORMAT. Major changes in the 2002 edition
relate to quality assurance and ease of use. Quality
assurance is established in conjunction with the MSJC Code and the
MSJC Specification contains specific instructions for the parties
involved. The phrase “When required” was eliminated.
Inclusion of this phrase in earlier editions made it necessary for
the user to extensively edit the MSJC Specification for
application to a particular project. Requirements Checklists and
Submittals The requirements checklists help the
designer to choose and specify the necessary products and
procedures found in the contract documents. Building codes
set minimum requirements to protect property and life safety.
However, written contract documents may have more restrictive
requirements than provided in the building code. Adjustments
for the particular project should be made by the designer by
reviewing the requirements checklists. There are two checklists, mandatory and
optional, that alert the designer to issues that must be
addressed. The mandatory list requires a choice on
inspection, testing, material selection and items not provided on
the drawings or details of the project. The most significant
change from the 1999 MSJC Specification in the mandatory checklist
is exclusion of determining specified compressive strength
compliance. In addition, the 1999 MSJC Specification
required that the level of quality assurance be specified. Part 1 - General In Part 1 it is stated that the MSJC
Specification covers requirements for materials and construction
of masonry elements. The provisions govern any project
unless other requirements are specifically stated in the contract
documents. (1.1) Definitions are provided and are
coordinated with those found in the MSJC Code. (1.2) All standards
referenced in the MSJC Specification are listed. These
standards include material specifications, sampling procedures,
test methods, detailing requirements, construction procedures and
classifications. The references are updated to the most
current edition at the time of the MSJC Code and Specification
approval. (1.3) The compressive strength of each wythe
of masonry must equal or exceed that specified by the engineer or
architect. The compressive strength must be verified by the
contractor by one of two methods: unit strength or prism
test. The unit strength method is a means to evaluate
the strength of masonry based upon the tested compressive strength
of individual units and the mortar type specified. The
prism test method requires the sampling and testing of masonry
prisms built with the same types of materials that are used in the
masonry construction. The MSJC Specification specifies prism
testing to be done in accordance with ASTM C 1314, Standard Test
Method for Compressive Strength of Masonry Prisms. (1.4B)
Adhesion of adhered veneer units to their backing is to be
determined in accordance with ASTM C 482, Test Method for Bond
Strength of Ceramic Tile to Portland Cement. (1.4C) Part 1 provides a list of items to be
included in project submittals. Submittals should include
mortar and grout mix designs and test results, masonry unit
samples and certificates, samples of metal items such as
reinforcement and wall ties. This also includes construction
procedures for cold- and hot-weather construction. (1.5) Quality assurance is required by the
MSJC Specification. The duties and services of the testing
agency, inspection agency and contractor are specified and are
dependent upon the level of quality assurance required.
Article 1.6A outlines the responsibilities of the testing
agencies. Article 1.6B specifies the
responsibilities of the inspection agency. Article 1.6C
contains the contractor's services and duties. The
contractor must employ an independent testing laboratory to
perform required tests, to document submittals, certify product
compliance, establish mortar and grout mix designs, provide
supporting data for changes requested by the contractor, or appeal
rejection of material found to be defective. The contractor
must include in the submittals the results of all testing
performed to qualify the materials and to establish mix designs.
Quality assurances are actions taken by the owner or the owner's
representative. They provide assurance that actions of the
contractor and supplier are in accordance with applicable
standards of good practice. Quality assurances are
administrative policies and responsibilities related to quality
control measures that meet the owner's quality objectives.
Quality control is the action taken by the producer or contractor.
This is simply systematic performance of construction, testing and
inspection to verify that proper materials and methods are used. Quality assurance involves inspection
and testing, preparation and erection of the masonry structure.
Inspection is assumed for every masonry project under the MSJC
Code, a change from previous masonry standards. The level of
inspection and the amount of testing depend upon the level of
quality assurance specified. The level of quality assurance
is determined according to facility function, as defined by the
general building code, and the method of design. The MSJC
Specification contains the same Quality Assurance tables that are
found in the MSJC Code. (1.6) Sample panels for masonry walls are
required for Level 2 or 3 quality assurance. The
construction of a grout demonstration panel, used to depart from
the requirements of Articles 3.5 C-E is also a part of quality
assurance. (1.6D) Requirements for delivery, storage and
handling of masonry materials are stated in order to avoid
contamination that might reduce the quality of the constructed
masonry. (1.7) Project-specific conditions such as support
of construction loads by the masonry and shoring and weather
exposure during construction must be addressed. Cold- and
hot-weather construction requirements are included and are
mandatory when they apply. The provisions for cold-weather
construction have been revised in the 2002 MSJC Specification.
Provisions for both cold-and hot-weather construction are
separated into preparation, and construction protection. In
most cases the methods to achieve the requirements are left to the
discretion of the contractor. (1.8) Part 2 - Products This section lists the available
American Society for Testing and Materials (ASTM) standards for
masonry materials, including masonry units, mortar, grout,
reinforcement and metal accessories. Specific requirements
are given if an appropriate ASTM standard does not exist.
Referenced ASTM standards for brick and tile are C 34, C 56, C 62,
C 126, C 212, C 216, C 652, and C 1088. There are provisions
for spacing of cross wires in joint reinforcement that are not
included in standard for this material. Minimum corrosion
protection requirements for metal items are stated including
galvanized and epoxy coatings. Requirements for
corrosion protection of bonded and unbonded prestressing tendons
are also included. Criteria are specified for prestressing
anchorages, couplers and end blocks. An accessories section
provides requirements on contraction joint material, expansion
joint material, asphalt emulsions, masonry cleaners and joint
fillers. (2.1-2.5) The MSJC Specification contains
requirements for the mixing of mortar and grout. Time of
mixing and additives to mortar are limited. The grout must
meet ASTM C 476 and be furnished and placed with a slump between 8
in. (200 mm) and 11 in. (275 mm). (2.6) Standard fabrication limits are stated
for reinforcement and for prefabricated masonry panels.
These include bend and hook requirements for reinforcing bars.
Prefabricated masonry panels must conform to the provisions of
ASTM C 901. (2.7) Part 3 - Execution The execution of the work includes
initial inspection; preparation; masonry erection; reinforcement,
tie and anchor installation; grout placement; prestressing tendon
installation and stressing procedure; field quality control; and
cleaning. Dimensional tolerances for foundations on which
masonry is placed are provided and should be measured prior to the
start of masonry work. (3.1) As part of the preparation
requirements, clay or shale masonry units having initial
absorption rates in excess of one gram per minute per in2,
as measured with ASTM C 67 must be pre-wetted, so the initial rate
of absorption will not exceed one gram per minute per in2
when the units are used. Cleanouts are required at the base
of masonry to be grouted whenever pour heights exceed 5 ft (1.5
m). (3.2) Standard requirements for good
workmanship are required by the MSJC Specification. These
include the requirement for completely filled mortar joints and
grouted spaces. Proper support of masonry and bracing during
construction is required but is not prescribed. Dimensional
tolerances for the masonry are listed to ensure structural
performance. The tolerances should not be used to establish
appearance criteria, unless specifically noted as such by the
project specifications. (3.3) Inspection of reinforcement and metal
accessories is required to ensure that they have been properly
placed and are free of materials that hinder bond.
Tolerances for locating and placing reinforcing steel, wall ties,
and veneer anchors are prescribed. Criteria for adjustable
wall ties, which are repeated from the MSJC Code, are included.
Placement requirements for veneer anchors have been added (3.4) Prior to grout placement, debris must
be removed from grout spaces. The grouting requirements
found in the MSJC Code are repeated in the MSJC Specification.
Maximum grout pour heights are determined by the type of grout
used and the dimensions of the grout space. Consolidation of
grout is required to fill voids created by the loss of water from
grout by absorption into the masonry. Alternate grout
placement requirements, established through the use of a grout
demonstration panel, are permitted. (3.5) Prestressing tendon installation and
stressing requirements include: tolerances; application and
measurement of the prestressing force; grouting bonded tendons;
and burning and welding operations. (3.6) As part of field quality control, the
specified compressive of masonry f'm
is verified in accordance with Article 1.6, Quality
Assurance; grout is sampled and tested in accordance with Articles
1.4B and 1.6. Provisions for cleaning exposed masonry
surfaces complete the MSJC Specification. (3.8) SUMMARY This Technical Notes provides an
overview to the criteria contained in the MSJC Code and
Specification. The discussion centers on the design
requirements to be followed by architects and engineers and the
masonry specifications to be implemented by the contractor during
construction. Changes to the Code and Specification in the
2002 editions are emphasized. The MSJC Code and
Specification provide the designer with coordination between the
design and construction phases of all masonry buildings. The information and suggestions
contained in this Technical Notes are based on the
available data and the experience of the engineering staff of the
Brick Industry Association. The information contained herein
must be used in conjunction with good technical judgment and a
basic understanding of the properties of brick masonry.
Final decisions on the use of the information contained in this Technical
Notes are not within the purview of the Brick Industry
Association and must rest with the project architect, engineer and
owner.
|
||||||||||||||||||||||||